Use INPUT to Turn on a OUTPUT Relay when the door is opened and turn the OUTPUT RELAY OFF when the door is closed again. (the concept could also be applied to a door that had been open to long)
Wire the N/O Door Contact to I/O INPUT 1
Wire the Alarm/Chime/Piezo to I/O Relay 1
When the door open it triggers INPUT 1 and EVENT Door Open Sensor Door Forced 1 and will Trigger OUTPUT Relay 1
When the Door is inspected and closed again , the event Door Open Sensor Door Closed 1 and will Trigger OFF OUTPUT Relay 1.
HOW TO DO IT in OMNIA
Create a profile for the IO8 and put it in.
IN THE PROFILE:
Create a DOS INPUT on IO8 1 or if you have MORE THAN ONE door to monitor, then create a DOS INPUT on IO8 2, etc etc
Create a (Action)Relay ON (activate) 65535 for relay 1 (and relay 2 if using INPUT 2 DOS)
Create a (Action)Relay OFF (deactivate) for relay 1 (and relay 2 if using INPUT 2 DOS)
GO TO READERS
Go to reader, IO8, Event Actions, Door Forced 1, select the Relay ON for relay 1
Go to reader, IO8, Event Actions, Door Closed 1, select the Relay OFF for relay 1
if you have more DOS IO...
Go to reader, IO8, Event Actions, Door Forced 2, select the Relay ON for relay 2 ( the event 2 will be created becuase you are on IO8 2 and so on...)
Go to reader, IO8, Event Actions, Door Closed 2, select the Relay OFF for relay 2